Power Switch
Contact Control
1. General Description
The iBoot-IO is a remote controlled power On / Off switch. One external control input is used to switch the
power ON and OFF. The iBoot-IO also provides a feedback circuit to verify the current power status. iBoot-IO
handles worldwide power from 105-240VAC. It is capable of switching up to 12 Amps at 120VAC and 10
Amps at 220 VAC. Screw terminals provide connection to the contact closure control and feedback circuit.
Power connections are made using supplied IEC-320 to NEMA 1-15 cables.
1.1. Covered Models
Four models are covered in this document. They differ in the type of input circuit used to control the power and
the default status of the power outlet when no control is provided.
SKU Model
Default Power
Control Input Type
1410037 iBoot-IO
ON
Dry Contact
1410039 iBoot-IO-OFF
OFF
Dry Contact
1410044 iBoot-IO-LS
ON
+3 to +12 VDC
1410045 iBoot-IO-OFFLS
OFF
+3 to +12 VDC
2. Connections
2.1. Connect Powered Device
Connect the device to be powered ON and OFF to the IEC receptacle marked Switched Outlet. An IEC 320 to
North American (NEMA 5-15) power cord is included for connecting the iBoot-G2 outlet to the device to be
controlled.
Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105-
125VAC or 10 Amps for 210-240VAC.
Connect Power Mains Connect the supplied power cord to the connector labeled AC Input, and the other end
to your AC source. If a power cord with a different terminating plug is required, be sure it is properly rated and
meets all the required local electrical standards.
Other Power Cords
Sourced Locally
Connect to Power Mains using
Supplied Cord
Connect Powered Device using
Supplied Cord
Page view 0
1 2 3 4 5 6 7

Summary of Contents

Page 1 - 2. Connections

Power Switch Contact Control 1. General Description The iBoot-IO is a remote controlled power On / Off switch. One external control input is used

Page 2 - 2.2. Inputs and Outputs

V150212E iBoot-IO Page 2 2.2. Inputs and Outputs The screw terminal blocks are on removable connectors for easy cable fabrication.

Page 3 -  Default Power OFF

V150212E iBoot-IO Page 3 2.6. Model iBoot-IO-LS 1410044  Default Power ON  DC Voltage (Wet) Control iBoot-IO-LS Function O Feedback Ou

Page 4 - 3. LED Indicators

V150212E iBoot-IO Page 4 3. LED Indicators LED OFF ON OK - Green Power Main Disconnected Power Main Connected PWR - Red Power Outlet Off Powe

Page 5 - 4. Mounting Options

V150212E iBoot-IO Page 5 4. Mounting Options iBoot-IO models are suitable for desktop or shelf mounting. A mounting kit for wall and DIN rail

Page 6 - 5. Specifications

V150212E iBoot-IO Page 6 5. Specifications 5.1. Physical Height 2.0” 60mm Width 3.2” 82mm Depth 4.2” 107mm Weight 8.6 oz 244g MTBF 40

Page 7

7. Technical Support and Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original de

Comments to this Manuals